Our Hosting Facility

Our Facility is a SSAE-16 Certified.
Monitoring 24 hours a day, 7 days a week, 365 days a year
Access restricted to authorized client personnel
Redundant Fiber paths. Bursting at 100 MBps in Internet Speed.
Navy Yard after hours security gate restricted access
Axis IP-based interior and exterior surveillance cameras
Entrance and exit controlled by HID contact-less access cards and multi-layer biometrics
Cabinet access controlled by a combination dial system
Multi-zone silent alarm & fire detection with automatic notification
Computer room air-conditioning (CRAC) units serviced by a 12-inch glycol distribution loop (850 ton capacity) driven by two redundant 2,240 GPM pumps
Twelve 20-ton, Four 30-ton Glycol CRAC units currently deployed
72º temperature 47% +/- 10% humidity automatic HVAC control
All units are N+1 configuration
Automatic FE-25 Clean Agent and dual interlocking pre-action fire suppression systems All MEP systems are monitored by Site Scan critical facility
Redundant electrical design and distribution:
Dual commercial power feeds
Dual 1.6MW backup diesel generators
Fully redundant 1 MW uninterruptable power supplies (UPS)
Fully redundant power distribution units (PDU)
Automatic switching from primary to backup power supply
Completely isolated ground system
Onsite fuel tanks.